Burner Controls - Retrofit Burner
Control SVST
Retrofit burner control systems are eligible for Enhanced Capital
Allowances, providing they are microprocessor based and are able
to continuously modulate burner output in response to measured boiler
temperature or pressure values, over the turn down ratio listed
in the appropriate section of the "Burners with Controls"
criteria.
The microprocessor must use PID control or more
advanced equivalents to control fuel and air flows. It must also
precisely control the air/fuel ratio, so oxygen and carbon monoxide
(CO) levels in the exhaust gases can be set at the values listed
in the appropriate section of the "Burners with Controls"
criteria.
All burner control elements including combustion
air dampers and fuel valves must be fitted with a precision servomotor,
which must be separately controlled and include positional feedback
control. The burner control system must incorporate facilities to
fully close air dampers on burner shutdown.
|