|
Burner Controls - Burner above
1200kW
Gas fired burners with a thermal output above 1,200kW, must have
microprocessor-based controls that continuously modulate burner
output in response to measured boiler temperature or pressure values,
over a turndown ratio of at least four to one. The microprocessor
must use PID control, or more advanced equivalents to control fuel
and air flows. It must also control the air/fuel ratio, so oxygen
levels in the exhaust gases can be set at a maximum of 3% at 100%
rating, 4% at 50% rating and 5.5% at 25% rating. Carbon monoxide
(CO) levels in the exhaust gases must not exceed 50 ppm throughout
the range. These combustion tests must be done in accordance with
the procedures laid down in EN676.
All gas burner control elements including combustion
air dampers and fuel valves must be fitted with a precision servomotor,
which must be separately controlled and include positional or flow
based feedback control. All burners must be fitted with air dampers
that fully close on burner shutdown.
Oil fired burners with a thermal output above
1,200kW must have microprocessor-based controls that modulate burner
output in response to measured boiler temperature or pressure values,
either continuously over a turndown ratio of at least 2.5 to one,
or step wise across at least three stages of output. The microprocessor
must use PID control, or more advanced equivalents to control fuel
and air flows. It must also control the air/fuel ratio, so oxygen
levels in the exhaust can be set at a maximum of 3% at 100% rating,
4% at 50% rating and 4.5% at 40% rating. Carbon monoxide (CO) levels
in the exhaust gases must not exceed 100 ppm throughout the range.
These combustion tests must be done in accordance with the procedures
laid down in EN267.
For oil burners, combustion air dampers and continuously
modulating fuel values (where used) must be fitted with a precision
servomotor, which must be separately controlled and include positional
or flow based feedback control. All burners must be fitted with
air dampers that fully close on burner shutdown.
In addition, all gas fired and dual fired burners
rated above 1,200kW must have a variable speed drive fitted to the
forced draught fan.
Important Note: Burners
with high turn down ratios should be only fitted to boilers that
are capable of working with equivalent turn down ratios.
|